Are transformer rooms required to be enclosed in fire-rated construction?

Transformer rooms are not automatically required to be enclosed in fire-rated construction. However, there are situations in which a transformer room may require a fire-rated enclosure.

When are electrical rooms, other than transformer rooms, required to be fire-rated?

Where an electrical vault is provided for conductors and equipment operating at over 600 volts, nominal, the vault must be enclosed with a minimum 3-hour fire-rated construction in accordance with NFPA 70. The 3-hour fire-rating is permitted to be reduced to a 1-hour fire-rated construction where the vault is protected with a suppression system.

Does NFPA 25 require water to be discharged every year during the annual fire pump flow test?

No, water is not required to be discharged every year during the annual fire pump flow test. NFPA 25 permits closed-loop flow testing every 2 out of 3 years. On the 3rd year, annual flow testing must be performed by discharging water via hose streams or to a drain or suction reservoir. In order to perform closed-loop testing, the fire pump must be equipped wit...